To avoid puncturing PEX tubing, use a skilled, careful concrete crew that’s familiar with pouring slabs over PEX circuits. If you detect a leak, you can fix it with a repair coupling or replace the circuit altogether.
How Do You Prevent Puncturing PEX Piping?
If you notice a drop of more than 5 PSI, there’s a leak somewhere in the circuit. If this happens, fix the damage section with either a repair coupling or a replacement circuit, and run the pressure test again.
If the initial pressure test is successful (no more than a 5 PSI drop), go ahead and lower the pressure to 25 PSI, while monitoring the pressure gauge for fluctuations. Now, your crews can finish the final preparations for getting ready for the slab pour.

How Do You Fix a Punctured PEX Tube AFTER a Concrete Pour?
After the concrete pour, you can fix a punctured section of PEX tube using the 4 steps below.
- Remove anywhere between 4 and 8 inches of concrete around the puncture.
- Cut out about ½-inch or the damaged tubing and reconnect the ends with a repair coupling.
- Protect the coupling with self-fusing tape, aka fire tape or self-vulcanizing tape.
- Place fresh concrete back into the opening. That’s it — you’re done!
Though repairing a punctured PEX tube may seem like an arduous task, it’s actually not — as long as you stick to the steps above!

Don't miss a thing!
Subscribe for exclusive content, insider industry news and limited edition webcasts.
Behind the Barrier: A Conversation on Oxygen-Barrier Tubing with Henco and Underfloor Solutions
At A Glance Aluminum oxygen protection: Henco PEX-AL-PEX uses a welded aluminum layer between two layers of PEX, creating an oxygen-tight barrier designed to help
Part 3: The Perfect Pour for Radiant-Heated Shops, Garages, and Barns
At A Glance Plasticizer mix protects radiant tubing integrity Heat-Sheet® Heavy panels stay rigid under buggy traffic Accurate yardage planning prevents mix inconsistencies Smart details:
Part 2: Smart Radiant Design for Shops, Barns, and Garages
At A Glance Organized manifold layout for clean zoning Engineered PEX spacing for balanced comfort Snap-in channels speed installation Efficient heat distribution = lower long-term